CONTROL CABLE – TINNED WIRE, TWO PAIR, 7 X AWG30, LSZH
Item Number: SG-8723
1) Conductor: Size :22AWG Tinned copper conductor to BS4109
2) Insulator: PE insulation Minimum Insulation Diameter: 1.3mm+/-5%
3) Individual Shield: 100% shield coverage (aluminum-polyester foil)
4) Ground Wire: 24AWG stranded tinned copper drain wire
5) Jacket Material: low smoke zero halogen compound
External Diameter: 5 mm +/-5%
ELECTRICAL CHARACTERISTICS: | |||||||
1.DC Resistance of Individual Conductor ( 20 Celsiu Degrees) | |||||||
Norminal Conductor Size | AWG22 | ||||||
Resistance Value | 14.7 ohms/1000ft | ||||||
2.DC Resistance Unbalance | Unbalance% Max Value ≤ 5.0 | ||||||
3.Insulation Resistance Between Conductor and insulator | |||||||
DC100-500V ≥ 1000MΩ.km ( 20 ゚C ) | |||||||
4.Electric Strength or Insulation(DC) | |||||||
Between Conductors: 1000V 1min Undisruptive | |||||||
Between Conductor and Shield: 3000V 1min Undisruptive | |||||||
5.Norminal Capacitance(nF/ft) | Between conductors | Average Value: 33 | |||||
6.Norminal Capacitance(nF/ft) | |||||||
Between conductors to other conductors & shield | Average Value: 62 | ||||||
7.Remote-End Crosstalk (150KHz) | |||||||
≥ 69dB/km Basic Unit or more than one pair Average Power Value | |||||||
≥ 68dB/km Average Power Value | |||||||
8. Norminal Velocity of Propagation | 66% | ||||||
9. Maximum Recommended Current | 2.3 Amps per conductors at temperature 25 ゚C | ||||||
10. Voltage Rating:300V | |||||||
11. Current Rating:11A |
MECHANICAL PROPERTIES: | |||||
1. Temperature Range | -20 to 80 Celsius Degree | ||||
2. Bending Radius | 10X Cable Diameter | ||||
3. Pull Tension | 63 Lbs, Maximum | ||||
4. Crush Resistance | 200 (N) per 100 cm Short Term | ||||
5. Twist Lay Length | Less than 80mm |
signalma –
The cable OD fits my conduits. The jacket is tested with fire without black smoke and spread. One improvement is the legend. It is not fully straightforward in certain stripe. Petra Ivanov from Bulgaria. May 2023
signalma –
I like the cable length up to 1000 meter. Good for my termination at site.